Handleiding
Je bekijkt pagina 68 van 149

Warnings(for using R290/R32 refrigerant only)
Extreme care shall be taken not to overfill the refrigeration 
system. Prior to recharging the system it shall be pressure 
tested with OFN. The system shall be leak tested on 
completion of charging but prior to commissioning. A follow 
up leak test shall be carried out prior to leaving the site.
14.Decommissioning
Before carrying out this procedure, it is essential that the 
technician is completely familiar with the equipment and all 
its detail. It is recommended good practice that all 
refrigerants are recovered safely. Prior to the task being 
carried out, an oil and refrigerant sample shall be taken in 
case analysis is required prior to re-use of reclaimed 
refrigerant. It is essential that electrical power is available 
before the task is commenced. 
a) Become familiar with the equipment and its operation.  
b) Isolate system electrically. 
c) Before attempting the procedure ensure that:
 Mechanical handling equipment is available, if required, for 
 handling refrigerant cylinders; 
 All personal protective equipment is available and being 
 used correctly; The recovery process is supervised at all 
 times by a competent person; 
 Recovery equipment and cylinders conform to the 
 appropriate standards. 
d) Pump down refrigerant system, if possible. 
e) If a vacuum is not possible, make a manifold so that 
 refrigerant can be removed from various parts of the 
 system. 
f)  Make sure that cylinder is situated on the scales before 
 recovery takes place. 
g) Start the recovery machine and operate in accordance 
 with manufacturer's instructions. 
h) Do not overfill cylinders. (No more than 80 % volume 
 liquid charge). 
i)  Do not exceed the maximum working pressure of the 
 cylinder, even temporarily. 
j)  When the cylinders have been filled correctly and the 
 process completed, make sure that the cylinders and the 
 equipment are removed from site promptly and all 
 isolation valves on the equipment are closed off. 
k) Recovered refrigerant shall not be charged into another 
 refrigeration  system unless it has been cleaned and 
 checked.
15.Labelling
Equipment shall be labelled stating that it has been 
de-commissioned and emptied of refrigerant. The label 
shall be dated and signed. Ensure that there are labels 
on the equipment stating the equipment contains 
flammable refrigerant.
16.Recovery
When removing refrigerant from a system, either for 
servicing or decommissioning, it is recommended good 
practice that all refrigerants are removed safely. 
When transferring refrigerant into cylinders, ensure that only 
appropriate refrigerant recovery cylinders are employed. 
Ensure that the correct number of cylinders for holding the 
total system charge is available. All cylinders to be used are 
designated for the recovered refrigerant and labelled for that 
refrigerant (i.e. special cylinders for the recovery of 
refrigerant). Cylinders shall be complete with pressure relief 
valve and associated shut-off valves in good working order. 
Empty recovery cylinders are evacuated and, if possible, 
cooled before recovery occurs. 
The recovery equipment shall be in good working order with 
a set of instructions concerning the equipment that is at hand 
and shall be suitable for the recovery of flammable 
refrigerants. In addition, a set of calibrated weighing scales 
shall be available and in good working order. Hoses shall 
be complete with leak-free disconnect couplings and in good 
condition. Before using the recovery machine, check that it 
is in satisfactory working order, has been properly 
maintained and that any associated electrical components 
are sealed to prevent ignition in the event of a refrigerant 
release. Consult manufacturer if in doubt.
The recovered refrigerant shall be returned to the refrigerant 
supplier in the correct recovery cylinder, and the relevant 
Waste Transfer Note arranged. Do not mix refrigerants in 
recovery units and especially not in cylinders. If compressors 
or compressor oils are to be removed, ensure that they 
have been evacuated to an acceptable level to make 
certain that flammable refrigerant does not remain within 
the lubricant. The evacuation process shall be carried out 
prior to returning the compressor to the suppliers. Only 
electric heating to the compressor body shall be employed 
to accelerate this process. When oil is drained from a 
system, it shall be carried out safely.
Note About Fluorinated Gasses
-Fluorinated greenhouse gases are contained in 
 hermetically sealed equipment. For specific information 
 on the type, the amount and the CO
2
 equivalent in tonnes 
 of the fluorinated greenhouse gas(on some models), 
 please refer to the relevant label on the unit itself. 
-Installation, service, maintenance and repair of this unit 
 must be performed by a certified technician.
-Product uninstallation and recycling must be performed 
 by a certified technician.
7
EN
Bekijk gratis de handleiding van Comfee CPPHA-09CRN7-L, stel vragen en lees de antwoorden op veelvoorkomende problemen, of gebruik onze assistent om sneller informatie in de handleiding te vinden of uitleg te krijgen over specifieke functies.
Productinformatie
| Merk | Comfee | 
| Model | CPPHA-09CRN7-L | 
| Categorie | Airco | 
| Taal | Nederlands | 
| Grootte | 17075 MB | 







