5
Warnings(for using R290/R32 refrigerant only)
1.Transport of equipment containing flammable refrigerants
See transport regulations
2.Marking of equipment using signs
See local regulations
3.Disposal of equipment using flammable refrigerants
See national regulations.
4.Storage of equipment/appliances
The storage of equipment should be in accordance with the 
manufacturer's instructions.
5.Storage of packed (unsold) equipment
Storage package protection should be constructed such 
that mechanical damage to the equipment inside the 
package will not cause a leak of the refrigerant charge.
The maximum number of pieces of equipment permitted to 
be stored together will be determined by local regulations.
6.Information on servicing
1)Checks to the area
Prior to beginning work on systems containing flammable 
refrigerants, safety checks are necessary to ensure that the
risk of ignition is minimised. For repair to the refrigerating 
system, the following precautions shall be complied with 
prior to conducting work on the system.
2)Work procedure
Work shall be undertaken under a controlled procedure so 
as to minimise the risk of a flammable gas or vapour being 
present while the work is being performed.
3)General work area
All maintenance staff and others working in the local area 
shall be instructed on the nature of work being carried out. 
Work in confined spaces shall be avoided. The area 
around the workspace shall be sectioned off. Ensure that 
the conditions within the area have been made safe by 
control of flammable material.
4)Checking for presence of refrigerant
The area shall be checked with an appropriate refrigerant 
detector prior to and during work, to ensure the technician 
is aware of potentially flammable atmospheres. Ensure 
that the leak detection equipment being used is suitable 
for use with flammable refrigerants, 
i.e. non-sparking, adequately sealed or intrinsically safe.
5)Presence of fire extinguisher
If any hot work is to be conducted on the refrigeration 
equipment or any associated parts, appropriate fire 
extinguishing equipment shall be available to hand. Have 
a dry powder or CO2 fire extinguisher adjacent to the 
charging area.
6)No ignition sources
No person carrying out work in relation to a refrigeration 
system which involves exposing any pipe work that 
contains or has contained 
flammable refrigerant shall use any sources of ignition in 
such a manner that it may lead to the risk of fire or 
explosion. All possible ignition sources, including cigarette 
smoking, should be kept sufficiently far away from the site 
of installation, repairing, removing and disposal, during 
which flammable refrigerant can possibly be released to the 
surrounding space. Prior to work taking place, the area 
around the equipment is to be surveyed to make sure that 
there are no flammable hazards or ignition risks. No 
Smoking signs shall be displayed.
7)Ventilated area
Ensure that the area is in the open or that it is adequately 
ventilated before breaking into the system or conducting 
any hot work. A degree of ventilation shall continue during 
the period that the work is carried out. The ventilation 
should safely disperse any released refrigerant and 
preferably expel it externally into the atmosphere.
8)Checks to the refrigeration equipment
Where electrical components are being changed, they shall 
be fit for the purpose and to the correct specification. At all 
times the manufacturer's maintenance and service 
guidelines shall be followed. If in doubt consult the 
manufacturer's technical department for assistance. The 
following checks shall be applied to installations using 
flammable refrigerants: 
The charge size is in accordance with the room size within 
which the refrigerant containing parts are installed; 
The ventilation machinery and outlets are operating 
adequately and are not obstructed;
If an indirect refrigerating circuit is being used, the 
secondary circuit shall be checked for the presence of 
refrigerant; Marking to the equipment continues to be 
visible and legible. Markings and signs that are illegible 
shall be corrected; 
Refrigeration pipe or components are installed in a 
position where they are unlikely to be exposed to any 
substance which may corrode refrigerant containing 
components, unless the components are constructed of 
materials which are inherently resistant to  being corroded 
or are suitably protected against being so corroded.
9)Checks to electrical devices
Repair and maintenance to electrical components shall 
include initial safety checks and component inspection 
procedures. If a fault exists that could compromise safety, 
then no electrical supply shall be connected to the circuit 
until it is satisfactorily dealt with. If the fault cannot be 
corrected immediately but it is necessary to continue 
operation, an adequate temporary solution shall be used. 
This shall be reported to the owner of the equipment so 
all parties are advised.  
Initial safety checks shall include:  
That capacitors are discharged: this shall be done in a 
safe manner to avoid possibility of sparking; 
That there no live electrical components and wiring are 
EN