Handleiding
Je bekijkt pagina 67 van 148

exposed while charging, recovering or purging the system; 
That there is continuity of earth bonding.
7.Repairs to sealed components
1)During repairs to sealed components, all electrical 
supplies shall be disconnected from the equipment being 
worked upon prior to any removal of sealed covers, etc. If it
isabsolutely necessary to have an electrical supply to 
equipment during servicing, then a permanently operating 
form of leak detection shall be located at the most critical 
point to warn of a potentially hazardous situation. 
2)Particular attention shall be paid to the following to ensure
that by working on electrical components, the casing is not 
altered in such a way that the level of protection is affected. 
This shall include damage to cables, excessive number of 
connections, terminals not made to original specification, 
damage to seals, incorrect fitting of glands, etc.  
Ensure that apparatus is mounted securely. 
Ensure that seals or sealing materials have not degraded 
such that they no longer serve the purpose of preventing the
ingress of flammable atmospheres. Replacement parts shall 
be in accordance with the manufacturer's specifications.
NOTE: The use of silicon sealant may inhibit the 
effectiveness of some types of leak detection
equipment. Intrinsically safe components do not have to 
be isolated prior to working on them.
8.Repair to intrinsically safe components 
Do not apply any permanent inductive or capacitance 
loads to the circuit without ensuring that this will not 
exceed the permissible voltage and current permitted for 
the equipment in use. Intrinsically safe components are 
the only types that can be worked on while live in the 
presence of a flammable atmosphere. The test apparatus 
shall be at the correct rating. Replace components only 
with parts specified by the manufacturer. Other parts may 
result in the ignition of refrigerant in the atmosphere from 
a leak.
9.Cabling
Check that cabling will not be subject to wear, corrosion, 
excessive pressure, vibration, sharp edges or any other 
adverse environmental effects. The check shall also take
into account the effects of aging or continual vibration 
from sources such as compressors or fans.
10.Detection of flammable refrigerants
Under no circumstances shall potential sources of ignition 
be used in the searching for or detection of refrigerant 
leaks. A halide torch (or any other detector using a naked 
flame) shall not be used.
11.Leak detection methods
he following leak detection methods are deemed 
acceptable for systems containing flammable refrigerants. 
Electronic leak detectors shall be used to detect flammable
refrigerants, but the sensitivity may not be adequate, or 
Warnings(for using R290/R32 refrigerant only)
may need re-calibration. (Detection equipment shall be 
calibrated in a refrigerant-free area.) Ensure that the 
detector is not a potential source of ignition and is suitable 
for the refrigerant used. Leak detection equipment shall be 
set at a percentage of the LFL of the refrigerant and shall be 
calibrated to the refrigerant employed and the appropriate 
percentage of gas (25 % maximum) is confirmed. Leak 
detection fluids are suitable for use with most refrigerants 
but the use of detergents containing chlorine shall be 
avoided as the chlorine may react with the refrigerant and 
corrode the copper pipe-work. If a leak is suspected, all 
naked flames shall be removed/ extinguished. If a leakage 
of refrigerant is found which requires brazing, all of the 
refrigerant shall be recovered from the system, or isolated 
(by means of shut off valves) in a part of the system remote 
from the leak. Oxygen free nitrogen (OFN) shall then be 
purged through the system both before and during the 
brazing process.
12.Removal and evacuation
When breaking into the refrigerant circuit to make repairs  
or for any other purpose conventional procedures shall be 
used. However, it is important that best practice is followed
since flammability is a consideration. The following 
procedure shall be adhered to:
 Remove refrigerant; 
 Purge the circuit with inert gas;   
 Evacuate; 
 Purge again with inert gas; 
 Open the circuit by cutting or brazing. 
The refrigerant charge shall be recovered into the correct 
recovery cylinders. The system shall be flushed with OFN 
to render the unit safe. This process may need to be 
repeated several times. Compressed air or oxygen shall 
not be used for this task.  
Flushing shall be achieved by breaking the vacuum in the 
system with OFN and continuing to fill until the working 
pressure is achieved, then venting to atmosphere, and 
finally pulling down to a vacuum. This process shall be 
repeated until no refrigerant is within the system. When 
the final OFN charge is used, the system shall be vented 
down to atmospheric pressure to enable work to take 
place. This operation is absolutely vital if brazing 
operations on the pipe-work are to take place. 
Ensure that the outlet for the vacuum pump is not close to 
any ignition sources and there is ventilation available.
13.Charging procedures
In addition to conventional charging procedures, the 
following requirements shall be followed.
Ensure that contamination of different refrigerants does 
not occur when using charging equipment. Hoses or lines 
shall be as short as possible to minimise the amount of 
refrigerant contained in them. 
Cylinders shall be kept upright.
Ensure that the refrigeration system is earthed prior to 
charging the system with refrigerant.
Label the system when charging is complete (if not already).
6
EN
Bekijk gratis de handleiding van Comfee CPPHA-07CRN7-L, stel vragen en lees de antwoorden op veelvoorkomende problemen, of gebruik onze assistent om sneller informatie in de handleiding te vinden of uitleg te krijgen over specifieke functies.
Productinformatie
| Merk | Comfee | 
| Model | CPPHA-07CRN7-L | 
| Categorie | Airco | 
| Taal | Nederlands | 
| Grootte | 17167 MB | 







