6. TROUBLESHOOTING
Problem Possible causes Possible solutions
1. The appliance does
not switch on when
pressing the on/o
button
The water tank is full,
and the indicator light is
ashing.
Empty the water tank.
The room temperature is
higher than the selected
temperature (in heat
mode).
Adjust the temperature.
The room temperature is
lower than the selected
temperature (in cool
mode).
Adjust the temperature.
2. It does not cool enough
There is a window or a
door open.
Make sure that all windows and
doors are properly closed.
There is a heat source
inside the room.
If possible, remove the heat
source from the room.
The exhaust hose is not
properly positioned or is
blocked.
Fit it properly or clean it.
The temperature is too
high.
Adjust the temperature.
The air outlet is blocked. Clean it.
3. The appliance makes
noise
The oor is not level or
not at enough.
If possible, place the device on a
at and level oor.
The sound comes from
the airow inside the
appliance.
This is normal.
4. E0 Code Room temperature sensor
fault.
Change the sensor (the
appliance can be used without
this sensor).
5. E1 Code Condenser temperature
sensor fault.
Change the sensor.
6. E2 Code The water tank is full
when the cool mode is in
operation.
Remove the rubber cap and
drain the water.
7. E3 Code Evaporator temperature
sensor fault.
Change the sensor.
8. E4 Code The water tank is full
when the heat mode is in
operation.
Empty the water.
1. Service information
1.1 Area verication
Before starting work on systems containing ammable refrigerants, safety checks are
necessary to ensure that the risk of ignition is minimised. Before repairing the cooling system,
the following precautions must be observed:
1.2. Work procedure
The work must be carried out in accordance with a controlled procedure to minimise the risk of
a ammable vapour or gas being present while the work is being carried out.
1.3. General workspace
All maintenance personnel and others working in the area should be briefed on the nature
of the work to be carried out. Work in conned spaces must be avoided. The area around the
workspace should be divided into sections. Ensure that conditions within the workspace are
safe by keeping ammable material under control.
1.4. Refrigerant verication
The area should be checked with an appropriate refrigerant detector before and during
work to ensure that the technician is warned of potentially ammable atmospheres. Ensure
that the leak-detection equipment used is suitable for use with ammable refrigerants, i.e.
non-sparking, adequately sealed, or intrinsically safe.