If the instructions provided with your gas hob state that the required
distance between the hob and the extractor must be greater than
650mm, then that is the distance which should be observed. This is
a legal requirement and may lead to your hob being disconnected
from the gas supply and the installation reported to RIDDOR (the
height should be measured from the top of the burners).
The width of any hob must not be greater than the width of the extractor
installed above it.
4.giF
Installation
IN THE ABSENCE OF ANY INSTRUCTIONS SUPPLIED WITH THE
GAS HOB, THE MINIMUM DISTANCE BETWEEN THE HOB AND
EXTRACTOR MUST BE AT LEAST 650mm.
When the extractor is to be installed above an electric hob, the
minimum distance between the hob and extractor must exceed 600mm
for ceramic and solid plate hobs and 550mm for induction Hobs.
When the extractor is to be installed above a gas hob, the minimum
distance between the hob and extractor must exceed 650mm.
Gas: 650mm recommended.
Electric: 600/550mm recommended.