Carrier TB-TM handleiding
Handleiding
Je bekijkt pagina 27 van 116

MAC Address and BACnet Device Instance Number
ComfortVu™ Thermostat Standard TB/TM Series Carrier Proprietary and Confidential CARRIER CORPORATION ©2025
Installation and Operation Guide All rights reserved
23
In an Analog Network Output microblock
To change the BACnet Device Instance Number from 16075 to 16113, the microblock’s address would be:
bacnet://16075/AV:42/present_value, or
bacnet://16075/BACnetDeviceInstanceNumber
Subsequent reads/writes of this value will need to be done with the new device instance:
bacnet://16113/AV:42/present_value, or
bacnet://16113/BACnetDeviceInstanceNumber
Bekijk gratis de handleiding van Carrier TB-TM, stel vragen en lees de antwoorden op veelvoorkomende problemen, of gebruik onze assistent om sneller informatie in de handleiding te vinden of uitleg te krijgen over specifieke functies.
Productinformatie
Merk | Carrier |
Model | TB-TM |
Categorie | Thermostaat |
Taal | Nederlands |
Grootte | 15804 MB |