Carel pYC mini handleiding

28 pagina's
PDF beschikbaar

Handleiding

Je bekijkt pagina 21 van 28
“pYC mini” +0300032IE - rel. 1.0 - 03.04.2025
9
ENG
Digital outputs
(*)
J6
NO1, NO2,
NO3, NO4
16A:
Panel: EN60730: 15A resistive, 250V, 100k cycles; UL60730: 15A resistive, 240Vac, 100k cycles;
Pilot duty B300, 6k cycles.
DIN: EN60730: 10A resistive, 250 V, 100k cycles; UL60730: 10A resistive, 240Vac,
100k cycles; 10FLA, 60LRA, 250Vac, 30K cycles; Pilot duty B300, 6k cycles.
8A:
EN60730: 5A resistive, 250Vac, 100k cycles; 5(4), 250Vac, 100k cycles; 4(2), 250Vac,
100k cycles; UL60730: 10A resistive, 250Vac, 100k cycles; 2FLA, 12LRA, 250Vac, 30k cycles
5A:
EN60730: 5A resistive, 250Vac, 50k cycles; 4(1), 230Vac, 100k cycles; 3(1), 230Vac, 100k cycles
UL60730: 5A resistive, 250Vac, 30k cycles; 1FLA, 6LRA, 250Vac, 30k cycles; Pilot Duty C300, 30k cycles
J7 NO5
J11
NO6
available
only on
DIN version
(*):
3-relay version connector J6, PANEL and DIN: R1+R2+R3 cannot exceed15 A max.
4-relay version connector J6, PANEL and DIN: R1+R2+R3+R4 cannot exceed 10 A max Tab. 2.k
Refer to the label for the actual relay rating.
Notice: in compliance with IEC/EN60079-15, in the 4-relay DIN version (connector J6), R1+R2+R3+R4 cannot
exceed 8 A max.
Non-volatile memory supply
EEPROM max num. of writing cycles 1 milion
Tab. 2.l
Warning: the operating system issues a warning when the write frequency is too high. The development system
includes libraries that enable handling this warning at the application level. It is recommended to use this feature to
preserve memory integrity. For more details, refer to the development environment’s online help.
Emergency power supply
J10 Ultracap module (opt., only available on the DIN versions) 13 Vdc +/-10%
Tab. 2.m
Probe and terminal power supply
5V
5 Vdc ± 2% to power the 0 to 5 V ratiometric probes.
Maximum current delivered: 35 mA protected against short-circuits
+V
8-11 V to power the 4-20 mA current probes
Max current delivered: 80 mA protected against short-circuits
VL not used
J8 user termianl power supply
Tab. 2.n
Cable lengths
Analogue inputs/outputs,
Digital inputs/outputs,
Probe power
<10m
Valve < 2 m, < 9m with shielded cable
BMS and Fieldbus serial cables <500m with shielded cable
Tab. 2.o
Conformity
Safety UL/IEC EN/UL60730-1, EN/UL60335-1
EMC CE EN61000-6-1, EN61000-6-2, EN61000-6-3, EN61000-6-4
Radio
RED EN301489-1/EN301489-17, EN300328
FCC Contains FCC ID: WAP2001
IC Contains IC: 7922A-2001
RCM Regulatory Compliance Mark (Australia & Nuova Zelanda)
SSRC Certificate of Conformity - State Radio Regulatory Commission (PR China)
Tab. 2.p