36
ENG
iJW +0300103EN rel. 1.1 - 31.03.2025
Index
When the controller is ON again, the compressor times are observed and all of the functions are reactivated, except for the de-
frost on start-up and compressor and evaporator fan delay at power on (par. c0).
Notice:
• the OFF command from digital input has priority over those from the keypad or supervisor;
• if the controller remains OFF for a longer time than the value set for parameter dI, a defrost is performed when the controller
is switched on again.
Code Desc. Def. Min Max UOM User User terminal
DIF Assign remote ON/OFF digital input - see DIA ... 0 4 - S NO
dI Maximum interval between consecutive defrosts 8 0 240 hours S YES
c0 Delay to enable solenoid/compressor and evaporation fans at power-on 0 0 240 min S NO
Curtain switch (par. DIG)
Digital input used to manage a curtain and switch from day to night (ECO).
During night status (ECO mode):
• the night-time set point Stn is used for control, calculated based on the set point St plus the off set defi ned by parameter r4
(Stn = St + r4) and r4d is used as the control diff erential. The control probe can also be modifi ed according to the setting of
parameter r6a (0 = virtual probe, 1 = probe), see the paragraph “Control”;
• the AUX or light output is deactivated according to the setting of parameter H8.
During day status:
• normal operation resumes: set point = St, virtual probe used as control probe;
• AUX or light output activated according to the setting of parameter H8.
Code Desc. Def. Min Max UOM User User terminal
DIG Assign curtain switch digital input - see DIA ... 0 4 - S No
H8 Output switched with time bands 0 = Light 1 = AUX 0 0 1 - S No
r4 Automatic night set point variation 0 -50/-90 50/90 °C/°F S No
r4d Temperature control diff erential in ECO mode 4/7.2 0.1/0.2 99.9/ 179.2 °C/°F S
r6a Night control probe:
0 = virtual probe Sv;
1 = air on probe Sr.
00 1 - S No
Start/stop continuous cycle (par. DIH)
When the contact is closed, the continuous cycle is activated, based on parameters cc and ccE (see "Functions").
When the contact opens again, the continuous cycle is deactivated.
Code Desc. Def. Min Max UOM User User terminal
DIH Assign start/stop continuous cycle digital input - see DIA ... 0 4 - S No
Generic alarm from digital input (par. DIS)
Activation of the alarm depends on parameter GFA_E. Activation of the alarm causes:
• message GHI shown on the display and service icon fl ashing;
• activation of the buzzer (see par. Hb);
• activation of the alarm relay (see par. DOb);
Code Desc. Def. Min Max UOM User User terminal
DIS Assign digital input for generic alarm from digital input - see DIA ... 0 4 - S No
GFA_E Generic alarm function, enable 0 = always; 1 = unit ON; 2 = unit OFF;
3 = defrost; 4 = not used; 5 = continuous cycle; 6 = duty setting; 7 = standby;
8 = control; 9 = door open; 10 = active alarm.
8 0 10 - S No
Low pressure switch (par. DIt)
If a low pressure switch is connected, the LP alarm is activated on opening. if pump down by pressure is enabled, the pressure
switch is used to switch off the compressor and the autostart procedure.
Code Desc. Def. Min Max UOM User User terminal
DIt Assign low pressure switch digital input - see DIA ... 0 4 - S No
Digital input for activating the output confi gured as AUX (par. DIU)
Digital input that can be used to activate/deactivate the output confi gured as AUX (parameter DOC).
Code Desc. Def. Min Max UOM User User terminal
DIU Assign AUX output activation digital input - see DIA ... 0 4 - S No
DOC Assign AUX auxiliary digital output - see DOA ... 0 6 - S No