Hecu +0300023EN rel. 1.2 - 14.12.2021
8.7 Alarm table
Screen
index
Enable screen Description Serious
alarm
Normal
alarm
Action Description
ALU01 Al_Conf_NOT_Admitted Confi guration not admitted x
ALU02 mAl_Reg_Probe_Miss Control probes missing x Unit shutdown At least one of the main probes is not
confi gured correctly: P_suc, P_disch
ALA01 mAl_Prb_Disch_Temp Discharge temperature probe
broken or disconnected
x No action on control
Relative functions disabled
Temperature probe at compressor outlet
faulty or not correctly confi gured
ALA02 mAl_Prb_Cond_Press Discharge pressure probe broken
or disconnected
x No action on control Discharge pressure probe faulty or incor-
rectly confi gured
ALA03 mAl_Prb_External_Temp External temperature probe
broken or disconnected
x Related functions disabled:
- control switch on T_ext in case
of P_disch failure on screen
Dg14
- capacitor speed up on T_ext
on screen Dg13
Temperature probe outside the condenser
faulty or not correctly confi gured
ALA04 mAl_Prb_Gen_Probe1 Generic probe A in board 1
broken or disconnected
x Related functions disabled
- if probe A is faulty or incor-
rectly confi gured the generic
function associated with it is no
longer active
General Purpose Probe A faulty or incor-
rectly confi gured
ALA05 mAl_Prb_Gen_Probe2 Generic probe B in board 1
broken or disconnected
x Related functions disabled
- if probe B is faulty or incor-
rectly confi gured the generic
function associated with it is no
longer active
General Purpose Probe B faulty or incor-
rectly confi gured
ALA06 mAl_Prb_Gen_Probe3 Generic probe C in board 1
broken or disconnected
x Related functions disabled
- if probe C is faulty or incor-
rectly confi gured the generic
function associated with it is no
longer active
General Purpose Probe C faulty or incor-
rectly confi gured
ALA07 mAl_Prb_Gen_Probe4 Generic probe D in board 1
broken or disconnected
x Related functions disabled
- if probe D is faulty or incor-
rectly confi gured the generic
function associated with it is no
longer active
General Purpose Probe D faulty or incor-
rectly confi gured
ALA08 mAl_Prb_Gen_Probe5 Generic probe E in board 1
broken or disconnected
x Related functions disabled
- if probe E is faulty or incor-
rectly confi gured the generic
function associated with it is no
longer active
General Purpose Probe E faulty or incorrect-
ly confi gured
ALA24 mAL_Prb_Suct_Press suction pressure probe broken
or disconnected
x Settable speed percentage in
case of faulty or disconnected
probe on screen Cag03
Compressor suction pressure probe faulty
or incorrectly confi gured
ALA25 mAl_Prb_Suct_Temp Suction temperature probe
broken or disconnected
x No action on control Compressor suction temperature probe
faulty or incorrectly confi gured
ALA31 mAl_Prb_Cond_Press_Bak Condensing pressure backup
probe broken or disconnected
x No action on control Backup pressure discharge probe faulty or
incorrectly confi gured.
Enabled and settable on screen Dag14