33
SD675650 ISSUE 6 M172 DELTA
The “Force compressor on when water heating is required” button toggles
between Yes and No. When set to Yes, e heat pump will be turned on to
provide water heating. This option only functions when priority is set to water.
The “Is Pool Pump Installed” button toggles between Installed and Not Installed.
If e Delta is not connected to pool water, is should be set to Not Installed.
This will prevent false alarms relating e pool water, and disable functions
at require e pool water to be connected. Pool water heat recovery, LPHW
heating and air-conditioning functions will be disabled.
The RCU set point is used when e Delta is built to be connected to RCUs.
Check wi e Danerm Group for additional information if is option is fitted.
The Economiser allows for free cooling using fresh air to cool e pool hall raer
an refrigerated air-conditioning using e heat pump.
For e Economiser to work two conditions need to be met.
1. The outdoor air temperature must be lower an e pool hall air
temperature. This difference is set by e Economiser Ambient Offset in
e screen shown above.
2. The pool hall air temperature needs to be higher an e user
temperature setting, but below e temperature at air-conditioning
turns on. This difference is set by e Economiser Air Offset in e screen
shown above.
The Delta control system measures e outdoor air temperature using a sensor
measuring e incoming fresh air temperature. The Economiser can be enabled/
disabled using e Economiser Enabled/Economiser Disabled button to toggle
between e two. When enabled, if e above conditions are met, e Delta will
increase e fresh air quantity to reduce e pool hall temperature.
Press e Arrow to return to e Advanced Setting screen or if noing else
needs to be changed press Home to return to e Home screen.
Button toggles
between YES and
NO
Button toggles between
Installed and Not Installed
Button toggles between Economiser
Enabled and Economiser Disabled
Press is button on e Advanced Settings menu.
Arrow icon
Return to
User Settings
Home icon
Return to
Home screen
MORE OPTIONS
Not installedNot installed
Economiser
Disabled
Economiser
Disabled