SD675650 ISSUE 6 M172 DELTA
DELTA SYSTEM OWNER INSTALLATION MANUAL
“Boiler Go” demand – terminals 6/7
For remote indication of Delta LPHW heat exchangers in operation, used to
indicate at e Delta requires LPHW to provide supplementary heating. This
could be used to indicate to a boiler, LPHW pump, LPHW control valve, or BMS
– whichever are required to enable LPHW flow to e Delta.
These are volt free contacts rated at 0.5A at 230V. Contacts close when LPHW
is required.
If e LPHW supply to e Delta is to be activated by e Delta control system,
ese terminals should be used to enable e LPHW supply. The specifics of is
connection depend on e design of e LPHW system.
If e LPHW supply to e Delta is not dependent on demand from e Delta
control system, ese terminals do not need to be used.
“Pool Pump Run” demand – terminals 8/9
(See page 51.)
“Time clock override” (remote Occupied/Unoccupied) – control
terminals 10/11
For remote control of e Delta Occupied/Unoccupied mode.
To enable Occupied mode, e remote switch should be closed. To enable
Unoccupied mode, e remote switch should be open. These terminals can be
connected to a user switch, pool cover micro-switch, BMS, or whatever system
determines e usage mode of e pool. The remote switch should be volt free
and suitable to switch 24Vdc.
If remote control of Occupied/Unoccupied is to be used, e User interface
should be set to Unoccupied. (See User Settings.)
If is facility is not required, ese terminals do not need to be used.
“Remote On/Off” – terminals 12/13
For remote control of On/Standby. To enable Delta to run, e remote switch
should be closed. To set e Delta to Standby, e remote switch should be
open. The remote switch should be volt free and suitable to switch 24Vdc.
Refer to Standby button function in e User instructions.
If remote On/Off control is required, e factory-fitted link wire should be
removed.
If is facility is not required, e factory-fitted link wire should be le in place.
Fire Alarm interface – terminals 14/15
For activating Standby mode in e event of a fire alarm. To enable e Delta
to run normally, e remote switch should be closed. To put e Delta into
Standby mode, e remote switch should be open. The remote switch should
be volt free and suitable to switch 230V. An alarm will show on e control
system when e fire alarm is activated.
If e fire alarm interface is required, e factory-fitted link wire should be
removed.
If is facility is not required, e factory-fitted link wire should be le in place.
“Remote Damper” control – terminals 19/20
(See page 52.)
“Volt free” status signals – terminals 21/22/23/24
For remote status indication. These are shared volt free contacts rated at a
maximum combined 0.5A at 230V.
Terminal 21 – Common.
Terminal 22 – Delta On. Contacts close when Delta is On.
Terminal 23 – Fault. Contacts close when a fault is active.
Terminal 23 – Air filter blocked. Contacts close when filter pressure drop
exceeds recommended level. Only available when e optional filter monitoring
sensors are fitted in e Delta.
If is facility is not required, ese terminals do not need to be used.