14
SD675650 ISSUE 6 M172 DELTA
DELTA SYSTEM OWNER INSTALLATION MANUAL
POOL OCCUPIED SYMBOL
POOL UNOCCUPIED SYMBOL
Whenever a floating pool cover is in use, e cover suppresses evaporation and
heat loss, so it is not necessary to maintain e air temperature higher an e
pool water. Significant running cost reductions can be achieved by reducing
e air temperature. Do not reduce e air temperature wiout a pool cover in
place.
Normal operation, wi e cover removed, is called Occupied Mode. Reduced
air temperature operation, wi e cover in place, is called Unoccupied Mode.
It is expected at e pool will be covered during Unoccupied periods, to
conserve energy and minimise evaporation. If Unoccupied Mode is used while
e cover is removed, increased power consumption and loss of ideal conditions
may result. The integral time clock on e control system allows fixed times to
be set for when e cover will be in place. If you have an automatic pool cover,
it may be possible to connect is to e Delta as described in section 3.8, to
automatically set Occupied and Unoccupied modes when e cover is moved.
The Delta operates in eier Occupied or Unoccupied Mode according to:
y User time period settings
y User override button
y Remote system connected to e interface terminals
In Occupied Mode, all functions operate according to User Settings.
In Unoccupied Mode, e following functions change:
y Pool hall air temperature setting reduced to e unoccupied temperature
setting (sometimes called night set back). The pool hall will not be cooled
to is temperature, but if heating is required, it will only heat to is lower
temperature setting.
y Refrigerated air-conditioning does not operate (Delta 4 upwards only). The
economiser will operate, if enabled.
y Fresh air is reduced to minimum, unless e user fresh air setting or air
quality sensor (if fitted) activate maximum fresh air.
y When water heating is required, ere is a delay of 60 minutes (adjustable)
in activating e pool pump and heating e water.
Going away for extended periods
Your Delta system, once commissioned, should never be turned off completely.
Even a cold pool will allow moisture to evaporate into e environment and if
is is not dealt wi expensive building damage may follow. If you go away for
extended periods or wish to take e pool out of commission, en you should
follow e following procedure:
Use a good swimming pool cover on e pool to minimise evaporation.
y Set e water temperature at 10°C
y Set e air temperature to 12-15°C
y Leave e humidity setting at 60-65%RH
y Leave e time clock setting in Unoccupied Mode
These settings will minimise energy usage whilst providing maximum
protection for your building.