6
3. PREPARATION
CAUTION
This unit has to be provided with a low voltage power source (AHU or other), refer to
section 5.2 for wiring.
1. Remove the unit from the box and inspect for damage. Installation hardware is located in a plastic bag
along with this guide, on top of the filler.
2. Put the unit down on a protected surface.
3. Open the unitās door and remove the filter to allow for more room to work in the electronic compartment.
š”
This unit reads temperature and relative humidity every hour and uses this data to choose the best time
of the day to ventilate, according to the chosen mode's preset limits.
4. Refering to the table below, choose the mode you want the unit to operate in and note it down in the
space provided for that purpose on the unit's label.
5. Refer to your local building code to determine the required airflow.
6. Refer to the tables below. Find out what speed and run time percentage the unit has to be set in to
provide the required airflow, and note down the chosen values in the space provided for that purpose
on the unit's label.
For example: If the required airflow is 90 CFM (circled below), the speed switch should be set to 180 CFM,
and the Run time % button, to 50%.
Run time % according to speed setting and required airflow
Speed
Setting
Required airflow (CFM)
30 35 40 45 50 55 60 65 70 75 80 85 90 95 100 105
130 CFM
25 30 30 35 40 40 45 50 55 60 60 65 70 75 80 80
180 CFM
20 20 20 25 30 30 35 35 40 40 45 50 50 55 55 60
Run time % button value
Speed
Setting
Required airflow (CFM)
110 115 120 125 130 135 140 145 150 155 160 165 170 175 180
130 CFM
85 90 90 95
100
----------
180 CFM
60 65 70 70 70 75 80 80 85 85 70 90 95 95
100
Run time % button value
Grayed out values are the
recommended settings and should be preferred.
Selected mode* Climatic Zones**
1 - Ashrae 2016
Zones 1-4
2 - Ashrae 2010 (factory setting)
Zones 1-4
3 - IRC / IMC 2012-2015
Zones 1-4
A - Comfort mode Hot / Humid #1
Zones 2A and 1
B - Comfort mode Hot / Humid #2
Zones 1 and 2A
C - Comfort mode Hot / Dry
Zone 2B
D - Comfort mode Mixed / Humid
Zones 3A, 4A, 3C and 4C
E - Comfort mode Mixed / Dry
Zones 3B and 4B
*Refer to the label on the inlet or to Appendix B for the full limits table.
**As defined by the Department of Energy. Refer to map in Appendix A.