3. INSTALL THE UNIT (CONTD)
3.6 INSULATED FLEXIBLE DUCTS INSTALLATION
CAUTION
Make sure the vapor barrier on the insulated ducts does not tear during
installation to avoid condensation within the ducts.
Use the following procedure for connecting the insulated flexible ducts to the unit
ports (exhaust to outdoors and fresh air from outdoors).
a) Pull back the insulation to expose the flexible duct.
b) Connect the interior flexible duct to the port using a tie wrap.
c) Carefully seal the connection with duct tape.
d) Pull the insulation over the joint.
e) Apply duct tape to the joint making an airtight seal. Avoid compressing the
insulation when pulling the tape tightly around the joint; compressed insulation
loses its R value and causes water dripping due to condensation on the exterior
surface of the duct.
a) b) c) d) e)
VJ0010
NOTE: In a retrofit installation, there maybe only one insulated duct already
installed for the unit ports.
If the unit is installed in the attic, connect this insulated duct to the
exhaust to outdoor port.
• If the unit is installed in the basement, connect this insulated duct to the
fresh air intake port.
3.7 EXTERIOR OPENING(S) INSTALLATION
3.7.1 TANDEM TRANSITION WITH DUAL EXTERIOR HOOD
If the joists are perpendicular to the ducts, or if the connection to the exterior
hood is in a limited area, the installation will need 2 exterior hoods (or soffit
grilles). Go to Point 3.7.2 or 3.7.4 for more details.