-4-
INDOOR MOUNTING ONLY
To achieve optimum protection, the air curtain should be
mounted on the inside of the building, ush to the wall and
as close to the top of the door opening as possible. To ensure
peak performance, keep the air stream free of obstructions.
The air curtain will not perform properly if negative air
pressure exists in the building. Under these conditions,
a means for makeup air to the building must be provided
so that the air pressure on both sides of the opening is in
balance.
Before mounting the air curtain, check the supporting structure
to verify that it has sucient load-carrying capacity to support
the weight of the air curtain(s). The mounting hardware
(supplied by others) should be capable of supporting a
minimum of three (3) times the weight of the air curtain.
See Table 1.
A. When determining the mounting location for the unit(s),
make sure that nothing interferes with the curtain of air
developed when the discharge vanes are directed from 0°
to 20° toward the door opening. If the air stream strikes any
obstruction (the top edge of the doorway, a door opening
device, etc.), the eectiveness of the unit will be greatly
reduced. See Figure 2.
B. For optimum performance, the bottom of the discharge
nozzle should be located in such a manner that it is spaced
out from the wall 3/8” for every inch the unit is above the
door opening.
C. Do not block (obstruct) the air intake screen. Insucient
airow can cause the unit to overheat.
D. Electric heated unit(s) shall:
1. Have a minimum clearance of at least 6’ between the
bottom of the unit and the oor.
2. Be installed Indoors Only.
E. The unit is shipped without the front and back trim in-
stalled to protect it from shipping damage. This trim need
not be installed until after the unit is hung. See Figure 3.
TABLE 1 - Weight Charts
Model
TOTAL NET WEIGHT
Ambient
Electric
Heat
Steam/Hot
Water Heat
ARE12-1036 101 105 126
ARE12-1042 108 112 136
ARE12-1048 114 118 145
ARE12-1060 134 138 177
ARE12-2060 171 179 214
ARE12-2072 182 190 229
ARE12-2078 188 196 238
ARE12-2084 194 202 247
ARE12-2096 205 213 264
ARE12-3096 245 257 304
ARE12-3108 273 285 337
ARE12-3120 285 297 354
ARE12-3132 297 309 376
ARE12-3144 308 320 393
ARE12-4144 364 380 449
Model
TOTAL NET WEIGHT (kgs)
Ambient
Electric
Heat
Steam/Hot
Water Heat
ARE16-1036 47 49 59
ARE16-1042 50 52 68
ARE16-1048 53 55 73
ARE16-1060 62 64 85
ARE16-2060 80 84 103
ARE16-2072 85 89 110
ARE16-2078 88 92 115
ARE16-2084 91 94 119
ARE16-2096 96 99 126
ARE16-3096 115 120 146
ARE16-3108 127 133 160
ARE16-3120 133 139 168
ARE16-3132 138 144 178
ARE16-3144 143 149 185
ARE16-4144 170 177 212
Figure 2 - General Mounting