A. A separate line voltage supply with a suitable branch
circuit protection device should be run directly from the
main electrical panel to the unit. A disconnect switch for
each branch circuit is a required part of this installation.
See the voltage label on the unit for circuiting and total
electrical load. The wiring diagram is located in the
wiring compartment, located on the top of the unit.
See Figure 7.
B. All eld wiring must be copper with a minimum
insulation of 60°C within approved conduit. If any of the
wire supplied in the unit must be replaced, it must be
replaced with copper wire with a minimum insulation of
90°C.
C. Electric, steam and hot water heated air curtains are
factory equipped with an unit mounted solid state
temperature sensor located internally to measure the
incoming (return) air stream.
D. Remove the wiring compartment cover.
E. Connect all supply and control circuit wires according to
the wiring diagram provided.
NOTE: For Electric, Steam and Hot Water heated air curtains
provided with an optional remote thermostat, mount and
wire the thermostat according to thermostat instructions
and wiring diagram.
For BACnet-IP Integration –
see XI - Appendix C, “BACnet-IP integration.
For Serial Network Connection - proceed to
XI - Appendix A, “Serial/Network Connection.
NOTE: The air curtain must have been ordered from the
factory with this option.
For Wall Mounted Touchscreen – proceed to
XI - Appendix B, “Wall Mounted Touchscreen.
if optional remote Touchscreen control of the
Intelliswitch™ has been ordered from the factory.
For Electric, Steam and Hot Water air curtains - proceed to
Section VI - Field Connections, otherwise proceed to
Section VII - Operating Instructions
A. ELECTRICALLY HEATED MODELS
The heater circuit may be controlled by an optional
remote thermostat or through the built-in Intelliswitch™
thermostat, which on model AI08 is located in the wiring
compartment, and on model AI10 is factory installed
inside the air curtain. Overheating protection is provided
by auto reset thermal cutouts built into the heater coil
assembly (see the wiring diagram located in the wiring
compartment). See Figure 7.
B. STEAM OR HOT WATER HEATED MODELS
An optional coil solenoid valve (by others or Berner)
may be controlled through the Intelliswitch™ or
independently. The Intelliswitch™ is capable of providing
the same voltage used for the motor to power a solenoid
load up to 5 amps. This call for heat may be controlled
by an optional remote thermostat or through the built-
in Intelliswitch™ thermostat located on top of the air
curtain. Piping should be done in accordance with local
codes, regulations and standard practices. Connect the
building system to the (3/4"-AI08 or 1"- AI10) MPT supply
and return header connections. See Figure 8.
VI. FIELD CONNECTIONS
Figure 7 - Electrical Connections
WIRING
COMPARTMENT
COVER
KNOCKOUTS
FOR POWER &
CONTROL
WIRING
Figure 8 - Steam / Hot Water Connections