Berner Architectural Elite 10 handleiding

16 pagina's
PDF beschikbaar

Handleiding

Je bekijkt pagina 4 van 16
-4-
II. MOUNTING INSTRUCTIONS (General)
INDOOR MOUNTING ONLY
To achieve optimum protection, the air curtain should be
mounted on the inside of the building, ush to the wall and
as close to the top of the door opening as possible. To ensure
peak performance, keep the air stream free of obstructions.
The air curtain will not perform properly if negative air
pressure exists in the building. Under these conditions,
a means for makeup air to the building must be provided
so that the air pressure on both sides of the opening is in
balance.
Before mounting the air curtain, check the supporting structure
to verify that it has sucient load-carrying capacity to support
the weight of the air curtain(s). The mounting hardware
(supplied by others) should be capable of supporting a
minimum of three (3) times the weight of the air curtain.
See Table 1.
IMPORTANT: A minimum of 4” is required above the top rear
corner of the air curtain for the installation and removal of the
inlet screen, and to ensure proper airow.
A. When determining the mounting location for the air
curtain(s), make sure that nothing interferes with the
curtain of air developed when the discharge vanes are
directed from 0° to 20° toward the door opening. If the
air stream strikes any obstruction (the top edge of the
doorway, a door opening device, etc.), the eectiveness
of the air curtain will be greatly reduced. See Figure 2.
B. For optimum performance, the bottom of the air curtain
(discharge nozzle) should be no more than 1” above the
top of the door opening with the air curtain(s) mounted
ush to the wall. If the air curtain must be mounted
higher, it must be spaced out from the wall 3/8” for
every inch the air curtain is above the door opening. See
Figure 3. For optimum protection, any void between the
air curtain and the wall should be sealed along the full
length of the air curtain.
C. Do not block (obstruct) the air intake screen. Insucient
airow can cause the unit to overheat.
D. The air curtain(s) shall:
1. Have a minimum clearance of at least 4” from
the sides and 4" from the top.
2. Have a minimum clearance of at least 6’ between
the bottom of the air curtain and the oor.
3. Be installed Indoors Only.
E. Proceed to either Section III - WALL MOUNTING or
Section IV - SUSPENDED MOUNTING
A. PREPARATION
1. Locate the wall mounting brackets. Two of the wall
mounting brackets are shipped already attached
to the back of the air curtain, and the third
is shipped loose and can be found in the carton that
contained the air curtain. See Figure 4.
Figure 2 - General Mounting
Figure 3 - Wall Mounting Location
TABLE 1 - Weight Chart
III. WALL MOUNTING
MODEL
Net Weight
MODEL
Net Weight
AE10
Ambient
AE10
Electric
AE10
Hot
Water
AE08
Ambient
AE08
Electric
AE08
Hot
Water
AE10-F-1036 100 104 125 AE08-F-1036 52 57 72
AE10-F-1042 112 116 140 AE08-F-1042 59 64 82
AE10-F-1048 125 129 156 AE08-F-1048 66 71 91
AE10-F-2060 168 176 205 AE08-F-1060 81 86 111
AE10-F-2072 193 201 239 AE08-F-1072 95 100 133
AE10-F-2084 218 226 270 AE08-F-2084 117 127 160
AE10-F-2096
244 252 302 AE08-F-2096 132 142 180
AE10-F-3096
262 274 320 AE08-F-2108 146 156 199
AE10-F-3108
287 299 351 AE08-F-2120 157 167 214
AE10-F-3120
306 318 374
AE10-F-3132
337 349 416
AE10-F-3144
362 374 447
AE10-F-4144
380 396 465
20°
AIR
Discharge
Nozzle
A
I
R
A
I
R
INTERIOR
EXTERIOR
6' minimum
AIR
Airstream
4" minimum
side & top
clearance from
combustible
material
AE08 - 7.125”
AE10 - 11”
AE08 - 10.75” MIN.
AE10 - 15” MIN.
WALL MOUNTING
BRACKET
MOUNTING
SCREWS
SPACER
MOUNTING
SCREWS
SEAL ALONG
LENGTH

Bekijk gratis de handleiding van Berner Architectural Elite 10, stel vragen en lees de antwoorden op veelvoorkomende problemen, of gebruik onze assistent om sneller informatie in de handleiding te vinden of uitleg te krijgen over specifieke functies.

Productinformatie

MerkBerner
ModelArchitectural Elite 10
CategorieNiet gecategoriseerd
TaalNederlands
Grootte3406 MB