Air stream too weak
Air stream hits obstruction
Negative pressure
Shaft rotating inside fan
One motor not operating
Nozzle not angled out far enough
Unit too powerful
Air movement too cold
Pushing air outside building
SEE AIR IS NOT HITTING FLOOR SYMPTOMS
Switch turned to “ON” position
Thermostat not set properly
Coils burned out due to lack of air
Automatic reset thermal cutout failed in open
position
Manual reset thermal cutout tripped
(if supplied)
Adjust nozzle to proper position, adjust motor
speed; see installation instructions
Remove obstruction or reposition air curtain
(move out 3/8” for every 1” up from the door)
Relieve negative pressure by providing makeup air
Tighten set screws
Repair or replace motor
Adjust nozzle angle to outside
Adjust motor speed
Add auxiliary heat to overcome wind chill factor
Adjust discharge angle back into building, adjust
motor speed
Replace switch or check wiring
Change thermostat setting
• Correctairowproblem;replacecoils
Replace automatic thermal cutout
Reset manual thermal cutout
AIR IS NOT HITTING
FLOOR
UNEVEN AIR
EXCESSIVE AIR
MOVEMENT AT
DOORWAY
ELECTRICALLY HEATED MODELS
NO HEAT
MINIMAL HEAT
EXCESSIVE HEAT
HOT WATER HEATED UNITS
EXCESSIVE HEAT
MINIMAL HEAT
NO AIR
Power supply line open (no power)
Fuse blown/circuit breaker tripped
Motor overload tripped
Failed switch
Check power source, check service disconnect,
check method of control in ON position
Replace fuse(s)/reset breaker
Internally protected motor - should reset
automatically after cool-down, if not, replace motor.
Replace switch
MOTOR RUNNING/FANS ARE NOT ROTATING
MINIMUM AIR
ELECTRICAL CONTROLS NOT FUNCTIONING WHEN DOOR IS OPEN
SYMPTOMS
REMEDY
CAUSE
• Brokenordamagedexiblehub
Shaft rotating inside fan
Selector switch is in off position
Door limit switch not operating
Air directional discharge vanes mis-adjusted
Inadequate intake clearance
Blower motor operates below speed
Fan rubbing against housing
Fan wheels clogged with dirt
Fan in backwards
Replace fan sleeve/reengage coupling
Tighten set screws/tighten fan on shaft
Turn switch to “ON” position
Repair or replace limit switch
Adjust vanes to proper position, see instructions
Move air curtain or remove obstruction
Provide adequate space for air curtain
Improper voltage
Free fan from housing
Clean and vacuum fan wheels
Check fans for blade curve toward discharge
Thermostat in wrong location - thermostat
too close to discharge
Improper voltage
Thermostat not set properly
Low entering air temperature
Incorrect speed range
Thermostat in wrong location
Thermostat not set properly
• Insufcientairovercoil
Improper voltage
Move thermostat away from air stream
Supply proper voltage
Change temperature setting
Based on unit temperature rise, reduce speed
Check Factory Menu speed range matches diagram
Move the thermostat closer to air stream
Change temperature setting
Remove restriction on intake
Supply proper voltage
• Reducehotwaterow
Clean intake and coils
• Increasewaterow
• Increasewaterow
X. TROUBLESHOOTING
Too high hot water pressure
Inadequateairow,nspluggedup,dirtycoils
Water temperature too low
Intake air below design temperature