BEKO BTFOG 120 G handleiding

120 pagina's
PDF beschikbaar

Handleiding

Je bekijkt pagina 54 van 120
54 / EN
Split type air conditioner / User Manual
13.1 Test run instructions
You should perform the Test run for at least
30 minutes.
1. Connect power to the unit.
2. Press the ON/OFF button on the remote
controller to turn it on.
3. Press the MODE button to scroll through the
following functions, one at a time:
COOL — Select lowest possible temperature
HEAT — Select highest possible temperature
4. Let each function run for 5 minutes, and
perform the following checks:
List of checks to
perform
Pass/Fail
No electrical leakage
Unit is properly grounded
All electrical terminals
properly covered
Indoor and outdoor units are
solidly installed
All pipe connection points do
not leak
Outdoor
(2):
Indoor
(2):
Water drains properly from
drain hose
All piping is properly insulated
Unit performs COOL function
properly
Unit performs HEAT function
properly
Indoor unit louvers rotate
properly
Indoor unit responds to
remote controller
Double-check pipe connections
During operation, the pressure of the refrigerant
circuit will increase. This may reveal leaks that
were not present during your initial leak check.
Take time during the Test Run to double-check
that all refrigerant pipe connection points do not
have leaks. Refer to Gas leak check section for
instructions.
5. After the Test run is successfully completed,
and you confirm that all checks points in List
of Checks to Perform have PASSED, do the
following:
a. Using remote control, return unit to normal
operating temperature.
b. Using insulation tape, wrap the indoor
refrigerant pipe connections that you
left uncovered during the indoor unit
installation process.
If ambient temperature is below 16°C (60°F)
You can’t use the remote controller to turn
on the COOL function when the ambient
temperature is below 16°C. In this instance, you
can use the Manual control button to test the
COOL function.
1. Lift the front panel of the indoor unit, and
raise it until it clicks in place.
2. The Manual control button is located on the
right-hand side of the unit. Press it 2 times to
select the COOL function.
3. Perform Test Run as normal.
Manual control button
13 Test Run

Bekijk gratis de handleiding van BEKO BTFOG 120 G, stel vragen en lees de antwoorden op veelvoorkomende problemen, of gebruik onze assistent om sneller informatie in de handleiding te vinden of uitleg te krijgen over specifieke functies.

Productinformatie

MerkBEKO
ModelBTFOG 120 G
CategorieAirco
TaalNederlands
Grootte11014 MB