52 / EN
Split type air conditioner / User Manual
12.1 Before test run
Only perform test run after you have completed
the following steps:
Electrical safety checks — Confirm that the
unit’s electrical system is safe and operating
properly
Gas leak checks — Check all flare nut
connections and confirm that the system is
not leaking
Confirm that gas and liquid (high and low
pressure) valves are fully open
12.2 Electrical safety checks
After installation, confirm that all electrical
wiring is installed in accordance with local
and national regulations, and according to the
Installation Manual.
12.2.1 Before test run
Check grounding work
Measure grounding resistance by visual
detection and with grounding resistance tester.
Grounding resistance must be less than 0.1Ω.
C
Note: This may not be required
for some locations in North
America.
12.2.2 During test run
Check for electrical leakage
During the Test run, use an electroprobe
and multimeter to perform a comprehensive
electrical leakage test.
If electrical leakage is detected, turn off the unit
immediately and call a licensed electrician to find
and resolve the cause of the leakage.
C
Note: This may not be required
for some locations in North
America.
A
Warning - risk of electric
shock
All wiring must comply
with local and national
electrical codes, and must
be installed by a licensed
electrician.
12 Electrical and gas leak checks