48 / EN
Split type air conditioner / User Manual
Piping extension beyond flare form
Outer diameter
of pipe (mm)
A (mm)
Min. Max.
Ø 6.35 (Ø 0.25”) 0.7 (0.0275”) 1.3 (0.05”)
Ø 9.52 (Ø 0.375”) 1.0 (0.04”) 1.6 (0.063”)
Ø12.7 ( Ø 0.5”) 1.0 (0.04”) 1.8 (0.07”)
Ø 16 ( Ø 0.63”) 2.0 (0.078”) 2.2 (0.086”)
Ø 19 (Ø 0.75”) 2.0 (0.078”) 2.4 (0.094”)
A
Flare form
Pipe
6. Place flaring tool onto the form.
7. Turn the handle of the flaring tool clockwise
until the pipe is fully flared.
8. Remove the flaring tool and flare form, then
inspect the end of the pipe for cracks and even
flaring.
Step 4: Connect pipes
When connecting refrigerant pipes, be careful
not to use excessive torque or to deform the
piping in any way. You should first connect the
low-pressure pipe, then the high-pressure pipe.
Minimum bend radius
When bending connective refrigerant piping, the
minimum bending radius is 10 cm.
≥10cm (4in)Radius
Instructions for connecting piping to indoor
unit
1. Align the center of the two pipes that you will
connect.
Indoor unit tubing
Flare nut
Pipe
2. Tighten the flare nut as tightly as possible by
hand.
3. Using a spanner, grip the nut on the unit
tubing.
4. While firmly gripping the nut on the unit
tubing, use a torque wrench to tighten the
flare nut according to the torque values in the
Torque requirements table below. Loosen
the flaring nut slightly, then tighten again.
10 Refrigerant piping connection