13
Trip Test of RCD (earth leakage circuit breaker)
Test current
switchable load
>30 mAAC at 230 VAC (load buttons
activated)
Single Pole Phase Test
Voltage range
100…690 VAC against earth
(2100-Alpha / 2100-Beta)
100…1000 VAC against earth
(2100-Gamma)
Frequency range 40 Hz…70 Hz
Acoustic
indication
yes
Indication Red LED
Continuity Test (Rx) / Diode Test
Range 0….500 kΩ
Tolerance 0% to +50%
Test current <5 μA
Acoustic
indication
yes
Diode test yes
Indication Yellow LED
Overvoltage
protection
690 V AC/DC (2100-Alpha / 2100-
Beta)
1000 VAC/1200 VDC (2100-Gamma)
Automatic power
ON
< 500 kΩ
Phase Rotation Indication
Voltage range
170…690 VAC phase to phase
(2100-Alpha / 2100-Beta)
170…1000 VAC phase to phase
(2100-Gamma)
Frequency range 40…70 Hz
Indication Green LEDs
Resistance measurement (Ω )
Low resistance indication “
(2100-Gamma only)
Resistance range
on LCD
0…1999 Ω
Resolution 1 Ω
Tolerance ± (5% rdg + 10 LSD) at 20°C
Temperature
coefficient
± (5 LSD / 10 K)
Test current <30 μA
Low resistance
indication
Acoustic indication <10…50 Ω
Overvoltage
protection
690 V AC/DC (2100-Alpha / 2100-Beta)
1000 VAC/1200 VDC (2100-Gamma)
Non contact cable break detector / EF (electric field)
(2100-Gamma only)
Voltage range 100…1000 VAC
Frequency range 50…60 Hz
Indication
3 levels shown by LCD segments as
following: