Refrigerated Prep Tables
Troubleshooting
Problem
Possible Cause
Possible Solution
Compressor is not
running.
Fuse blown or circuit breaker tripped. Replace fuse or reset circuit breaker.
Power cord unplugged. Plug in power cord.
Thermostat set too high. Set thermostat to lower temperature.
Cabinet in defrost cycle. Wait for defrost cycle to finish.
Condensing units run for
long periods of time.
Excessive amount of warm product
placed in cabinet.
Allow adequate time for product to cool down.
Prolonged door opening or door ajar.
Ensure doors are closed when not in use. Avoid
opening doors for long periods of time.
Door gasket(s) not sealing properly.
Ensure gaskets are snapped in completely.
Remove gasket and wash with soap and water.
Check condition of gasket and replace if necessary.
Dirty condenser coil. Clean the condenser coil. (Page 8)
Evaporator coil iced over.
Unplug unit and allow coil to defrost. Make sure
thermostat is not set too cold. Ensure that door
gasket(s) are sealing properly.
Cabinet temperature is
too warm.
Thermostat set too warm. Set thermostat to lower temperature.
Air flow blocked.
Re-arrange product to allow for proper air flow.
Make sure there is at least four inches of clearance
from evaporator.
Excessive amount of warm product
placed in cabinet.
Allow adequate time for product to cool down.
Fuse blown or circuit breaker tripped. Replace fuse or reset circuit breaker.
Dirty condenser coil. Clean the condenser coil. (Page 8)
Evaporator coil iced over.
Ensure doors are closed when not in use. Avoid
opening doors for long periods of time.
Low refrigerant levels.
Contact a service technician to check refrigerant
levels.
Door is slightly ajar. Make sure door is completely closed.
Condensation is
collecting on the cabinet
and/or floor.
Gasket is not sealing properly. Clean, repair, or replace the gasket as necessary.
Relative humidity is above 60%.
Move unit to area below relative humidity or lower
humidity level.