ACRC300 Series, ACRC600 Series Technical Data
Temperature
DB, WB °C
F)
CW Delta T °C
(°F)
Total Net
Capacity kW
(BTU/hr)
Sensible Net
Capacity kW
(BTU/hr)
Sensible Heat
Ratio SHR
CW Flow Rate
l/s (GPM)
Total CW
Pressure Drop
kPa (ft H
2
O)
11.1°C (20°F) 31.0 (106000) 30.3 (104000)
0.98
0.70 (11.0) 27.7(9.3)
43.33°C DB, 22.4°C WB (110°F DB, 72°F WB)
7.7°C (14°F) 38.5 (131000) 37.8 (12900)
0.98
1.24 (19.6) 75.8 (25.4)
8.8°C (16°F) 37.0 (126000) 36.3 (124000)
0.98
1.04 (16.4) 55.7 (18.7)
10.0°C (18°F) 35.7 (122000) 35.0 (119000)
0.98
0.89 (14.1) 42.6 (14.3)
11.1°C (20°F) 34.5 (118000) 33.8 (115000)
0.98
0.78 (12.3) 33.5 (11.2)
46.11°C DB, 23.3°C WB (115°F DB, 74°F WB)
8.8°C (16°F) 40.5 (138000) 39.6 (135000)
0.98
1.13 (17.9) 64.7 (21.7)
10.0°C (18°F) 39.1 (133000) 38.3 (131000)
0.98
0.97 (15.4) 49.7 (16.7)
11.1°C (20°F) 37.9 (129000) 37.2 (127000)
0.98
0.85 (13.5) 39.4 (13.2)
48.89°C DB, 23.9°C WB (120°F DB, 75°F WB)
8.8°C (16°F) 43.9 (150000) 43.0 (147000)
0.98
1.22 (19.4) 74.4 (24.9)
10.0°C (18°F) 42.6 (145000) 41.7 (142000)
0.98
1.05 (16.7) 57.2 (19.2)
11.1°C (20°F) 41.4 (141000) 40.6 (138000)
0.98
0.93 (14.7) 45.8 (15.4)
NOTE: Any CW flow rate of 3.0 GPM–5.0 GPM may have increased error in
Flow Rate and Power Calculation. A Fluid Flow Fault may result. Any flow rate
under 3.0 GPM may also display as 0 in Flow Rate and Power Calculation.
44 990-5792B-001