5.3.4 Automatic Defrost
At low room temperatures, frost may
buildup at the evaporator during
operation. The unit will automatically
start defrosting and the POWER LED
blinking. The defrost control sequence
is as follows:
A.When the unit operates in the
cooling operation, drying operation, the
ambient temperature sensor senses
the evaporator coil temperature is
below -1°C, after the compressor will
stop operating for 10 minutes or the coil
temperature up to 7ºC, the unit restart
to cool operating mode.
B.When the unit operates in the hea-
ting operation, drying operation, once
the coil temperature sensor senses the
temperature of the evaporator is below
40ºC and the differential temperature
between coil temperature and room
temperature is below 19ºC after the
compressor operation for 20minutes,
the unit start defrosting for 5 minutes
and the power indicator blinking.
5.3.5 Overload Protection
In the event of a power loss, to protect
the compressor there is a 3-minute
delay until the compressor restarting.
5.4 DRAINAGE
Manual drainage:
1)When the machine stops after the
water is full, please unplug the power
plug.
Notes: Please move the machine
carefully, so as not to spill the water in
the water pan at the bottom of the unit.
2)Place the water container below the
side water outlet behind the unit.
3)Unplug the water plug, the water
will automatically ow into the water
container.
Notes:
1. Keep the water plug properly.
2. During drainage, the unit can be
tilted slightly backwards.
3. If the water container cannot hold all
the water, before the water container
is full, stuff the water outlet with the
water plug as soon as possible to
prevent water from owing to the
oor or the carpet.
4)When the water is discharged, stuff
the water plug.
Notes: 1. Restart the machine after the
water plug and drainage cover are
installed, otherwise condensate water
of the machine will ow to the oor or
the carpet.
FIGURE Nº13
Continuous drainage
The self-evaporating system uses the
collected water to cool the condenser
coils for better efcient performance. It
is no need to empty the drainage tank
in cooling operation except in drying
operation and high humidity condi-
tions. The condensate water evaporates
at the condenser and evacuated
through the exhaust hose.
For continuous operation or unatten-
ded operating in drying operation,
please connect the attached drain
hose to the unit. Condensate water can
be automatically ow into a bucket or
drain by gravity.
■ Switch off the unit before operating.
■ Remove the plug of the water outlet
opening, and keep it in safe area.
■ Securely and properly connect the
drain hose and make sure it is not