'ERROR' and WARNING INDICATORS
Error Code Problem Cause Corrective Action
'ERROR' AND WARNING
INDICATORS
High pressure
Blocked COND filter.
Blocked / kinked exhaust duct.
Ambient temperature is too high.
Clean the COND filter.
Ensure exhaust duct is not blocked
/ kinked. Do not use the air
conditioner if ambient temperature
is higher than 113℉.
Low pressure Verify Electrical.
Refrigerant may be low
or empty.
Verify Power (Voltage / Amps).
Check refrigerant level and
refrigerant leakage.
Clean Filter and Coil.
Check Evaporator Filter.
Check Evaporator Coil.
Compressor
(HSC-36P X)
EOCR is operated.
Low supply voltage.
Magnet switch is
inoperative.
Check voltage is in
220/480 V~ (±10%)
Check capacitor. Check compressor.
Check Magnet switch.Check wiring.
COND Fan Motor
(HSC-36P X)
EOCR is operated.
Low supply voltage.
Magnet switch is
inoperative.
Check voltage is in
220/480 V~ (±10%)
Check capacitor. Check Cond Fan Motor.
Check Magnet switch. Check wiring.
EVA Fan Motor
(HSC-36P X)
EOCR is operated.
Low supply voltage.
Magnet switch is
inoperative.
Check voltage is in
220/480 V~ (±10%)
Check capacitor. Check Eva Fan Motor.
Check Magnet switch. Check wiring.
Water full Condensate pump is full. Check the condensate pump or
water hose is bent.
Tank Position Condensate pump is not
connected.
Check condensate pump
connection.
Fire alarm signal Fire alarm signal is received
from Fire alarm system.
Reset unit by pushing and
holding the "OFF TIMER" button
for 5 seconds.
Anti-Freezing
alarm
Evaporator is below 25℉
(-2℃) due to being used in a
low ambient temperature area.
Do not use the unit in an ambient
temperature less than 65℉ (18℃).
Check refrigerant level.
Reverse phase
(HSC-36P X,
HSC-60P 220/1 X)
The 3 phase circuit is not
correctly connected.
Check wiring.
RT sensor If the RT sensor is short
circuited or cut 'E3 rt'
displayed and the 'Error'
LED will be on.
Exchange RT sensor in digital
controller.
OT sensor If the OT sensor is short
circuited or cut 'E3 Ot'
displayed and the 'Error'
LED will be on.
Exchange OT sensor.
AF sensor If the AF sensor is short
circuited or cut 'E3 A1'
displayed and the 'Error'
LED will be on.
Exchange AF sensor.