ERROR SIGNAL CONNECTION
The unit will output an Error signal (normal open dry contact) when an "Error" has occurred,
to show what the failure is on the unit.
1. Open the power box cover.
2. Use recommended error signal wire size from 16 AWG to 26 AWG for a solid wire,
or 16 AWG to 22 AWG for a stranded wire with ring terminal for #5 stud size.
3. Connect the end of the error signal wire to ER1 and ER2, and the other end to the compatible
with varoius warning devices such as alarm speaker, light indicators, and etc.
● Output terminal ER1 and ER2
● Connecting Error Signal with Warning Device
ERROR SIGNAL CONNECTION