'ERROR' and WARNING INDICATORS
Error Code Problem Cause Corrective Action
High pressure Blocked COND filter.
Blocked / kinked exhaust duct.
Ambient temperature is too high.
Clean the COND filter.
Ensure exhaust duct is not blocked
/ kinked.
Do not use the air conditioner if
ambient temperature is higher
than 113℉.
Low pressure Verify Electrical.
Refrigerant may be low
or empty.
Verify Power (Voltage / Amps).
Check refrigerant level and
refrigerant leakage.
Clean Filter and Coil.
Check Evaporator Filter.
Check Evaporator Coil.
BLDC Motor If BLDC motor is not
operated, 'E5' displayed
and the 'Error' LED will be on
Check or change BLDC motor
Water full Water tank is full. Empty the water tank.
Align water tank Water tank is not
positioned correctly.
Place the water tank
in right position.
Fire alarm signal Fire alarm signal is detected
from Fire alarm system.
Reset unit by pushing and
holding the "OFF TIMER" button
for 5 seconds.
Anti-Freezing
alarm
Evaporator is below 25℉
(-2℃) due to being used in a
low ambient temperature area.
Do not use the unit in an ambient
temperature less than 61℉ (16℃).
Check refrigerant level.
AF1 sensor If the AF1 sensor is short
circuited or cut 'E3 A1'
displayed and the 'Error'
LED will be on.
Exchange AF1 sensor.
RT sensor If the RT sensor is short
circuited or cut 'E3 rt'
displayed and the 'Error'
LED will be on.
Exchange RT sensor in digital
controller.
OT sensor If the OT sensor is short
circuited or cut 'E3 Ot'
displayed and the 'Error'
LED will be on.
Exchange OT sensor.
'ERROR' AND WARNING
INDICATORS