FIRE ALARM
15
When the signal from the fire alarm system is detected,
the unit turns off and does not operate until the unit has been RESET.
1. Remove the 'Cap' on the 'Fire Alarm Cover'.
2. Use recommended fire alarm wire size from 16 AWG to 26 AWG for a solid wire,
or 16 AWG to 22 AWG for a stranded wire with ring terminal for #5 stud size.
3. Connect fire alarm to terminal FA1 and FA2.
Remove
Cap
Close
Cover
Wire
Input
Fire alarm
Signal
Terminal
FA1
FIRE ALARM SYSTEM
FA2
ALARM
FA1 FA1
FIRE ALARM SIGNAL INPUT NORMAL CONDITION
CLOSED OPEN
FA2 FA2
● Input terminal FA1 and FA2
● Connecting the fire alarm wire from fire alarm system
FIRE ALARM