Advantech WISE-S100 handleiding
Handleiding
Je bekijkt pagina 23 van 32

15 WISE-S100 Series User Manual
Chapter 4 Firmware Specification
4.3 Light Sensor Channel Configuration
Parameter Description Values Default
Channel switch Enable/disable this channel Enable/Disable Enable
High limit
The state becomes high if illumination
is over the high limit
0~83865, Unit: lux 550
Low limit
The state becomes low if illumination
is below low limit
0~83865, Unit: lux 450
Fast Blink
Frequency
Fast blink frequency threshold 0.2 ~ 2.55 Hz 2 Hz
mode Light sensor state query mode
On/Off mode
On/Off/Blink mode
On/Off/
Blink mode
Delay time
In On/Off/Blink mode, if within delay
time the state keeps high/low, the
state becomes high/low
1s ~ 5s
Unit: second
2s
Filter
How many consecutive events are
required to trigger the state
(implement by sensor)
0: disable
1: 2 * conversion time
Disable
Illumination
option
Whether to get illumination
0: disable
1: enable
disable
Normal state
Which state should save more power,
off or on
Off/On off
Note! Because of the resolution of the sensor is not always less than 1 as fol-
lowing table, the user setting and actual light sensor setting might be
inconsistent. For example, if a user sets 83850 on high limit, FW set
83845.12 on sensor but still show 83850 to user.