WISE-4671 User Manual 22
3.5.4 WISE-S672 I/O Module
3.5.4.1 Digital Inputs
Channels: 6
Logic Level (Dry Contact):
– 0: Open
– 1: Close DI COM
Non-isolation
Supports 32-bit counter input function (maximum signal frequency: 200 Hz)
Supports keep/discard counter value when power OFF. (Only work with line
powered model)
Supports frequency input function (maximum signal frequency: 200 Hz)
Supports inverted digital input status
3.5.4.2 COM #1
Port Type: RS-485
Baud Rate (bps): 1200, 2400, 4800, 9600, 19200, 38400, 57600, 115200
Data Bits: 8
Stop Bits: 1, 2
Parity: None, Odd, Even
Flow Control: Auto flow control
Signals: DATA+ and DATA-
Protection: 15 kV ESD
Supported Protocols:
– Modbus/RTU (Up to 32 addresses with a maximum of 8 instructions)
3.5.4.3 COM #2
Port Type: RS-485 or RS-232
Baud Rate (bps): 1200, 2400, 4800, 9600, 19200, 38400, 57600, 115200
Data Bits: 8
Stop Bits: 1, 2
Parity: None, Odd, Even
Flow Control: Auto flow control (RS-485 only)
Signals: DATA+ and DATA-
Protection: 15 kV ESD
Supported Protocols:
– Modbus/RTU (Up to 32 addresses with a maximum of 8 instructions)