WISE-4671 User Manual 20
> 2M Ω (voltage)
240 Ω (external resistor for current)
Isolation Voltage: 2000 V
RMS
Common Mode Voltage: 350 V
DC
Drift:
Unipolar ±100ppm
Bipolar ±50ppm
Burn-Out Detection: Yes (4 ~ 20mA only)
Supports data scaling and averaging
3.5.2 WISE-S615/WISE-S615T RTD I/O Module
3.5.2.1 Analog Input
Channels 4 differential
Input Connections 2, 3-wire
Input Impedance 10 MΩ
Resolution 15 bits
Sampling Rate 1 Sample/s (MAX)
RTD Types and Temperature Ranges
Pt 100 RTD
RTD 100 (a = 0.00385) -200°C to 600°C
RTD 100 (a = 0.00392) -200°C to 600°C
Pt 1000 RTD
Pt -40°C to 160°C
Accuracy ±0.1% FSR
CMR @ 50/60 Hz 90 dB
NMR @ 50/60 Hz 60 dB
Span Drift ± 25 ppm/°C
3.5.3 WISE-S617/WISE-S617T I/O Module
3.5.3.1 Digital Input
Channel: 2
Logic Level (Dry Contact):
0: Open
1: Close to DI COM
Non-isolation
Supports 32-bit counter input function (maximum signal frequency: 200 Hz)
Supports keep/discard counter value when power OFF. (Only work with line
powered model)
Supports frequency input function (maximum signal frequency: 200 Hz)
Supports inverted digital input status