WISE-2460 User Manual 12
2.5 WISE-2460 Sensor Calibration Mode
WISE-2460 builds-in calibration mode and allow users to calibrate the sensor by
themselves. There are few things need to check before using this function.
1. Need to make sure the values from your shaker are correct.
2. Fix your WISE-2460 on shaker.
3. Set your shaker output in 1g@500Hz condition.
4. Click “Start Calibration” button on WISE Studio and wait around 5 seconds for
data processing.
5. Check “Average Sensitivity” value, and copy the “Average Sensitivity” value
to “User Sensitivity” box, and click “Submit” for writing this value into your
WISE-2460.
6. User can also restore default sensitivity by click “Reset Sensitivity” button.
2.6 Get time-domain raw data from WISE-2460
User can get the real time time-domain raw data from WISE-2460 directly. It will take
around 40s for getting one raw data from WISE-2460. User can refer following pro-
cess for getting the data on WISE Studio.
1. Click “Query Data” from WISE Studio, and WISE-2460 Data Query window will
pops up.