Advantech LEO-S592-AQ handleiding
Handleiding
Je bekijkt pagina 17 van 32

www.advantech.com
17
Besides numerical calibration, ToolBox provides more calibration methods for CO
2
:
Manual Calibration: Put the device in an open outdoor environment for more than 10 minutes
and click this button to calibrate the CO
2
value.
Restore Factory Calibration: Clean the manual calibration and turn back to factory calibration.
Auto Background Calibration: When enabled, keep the device work in a well-ventilated
environment for 180 hours (around 7 days), then disable the calibration.
4.5.3 Threshold Settings
Go to “Device Settings -> Basic” of ToolBox software or “Device -> Settings -> Threshold
Settings” of ToolBox App to enable the threshold settings and input the threshold.
For temperature, it will upload the current data once instantly when temperature is over or below
the threshold. Note that when you change the temperature unit, please re-configure the
threshold.
For CO
2
, TVOC, PM2.5, PM10 and HCHO, it supports defining Excellent, Polluted and Bad
threshold for traffic light, buzzer and screen alarms. Besides, when one of concentrations of air
pollutants exceeds the Bad threshold, LEO-S592-AQG0 will upload the current data once
instantly.
Bekijk gratis de handleiding van Advantech LEO-S592-AQ, stel vragen en lees de antwoorden op veelvoorkomende problemen, of gebruik onze assistent om sneller informatie in de handleiding te vinden of uitleg te krijgen over specifieke functies.
Productinformatie
Merk | Advantech |
Model | LEO-S592-AQ |
Categorie | Niet gecategoriseerd |
Taal | Nederlands |
Grootte | 4130 MB |