Min/Max: UNIT16/10,
unit: °C
Alarm Reporting
Interval: UINT16,
unit: min
Temperature_change threshold:
CTRL(1B)+0000+Change_value(2B)+00000000 (4B)
CTRL:
58=Temperature_change Threshold of CH1 Enabled
18=Temperature_change Threshold of CH1 Disabled
60=Temperature_change Threshold of CH2 Enabled
20=Temperature_change Threshold of CH2 Disabled
Change value:
UNIT16/10, unit: °C
68 (Data Storage)
00: disable, 01: enable
69 (Data Retransmission)
00: disable, 01: enable
6a (Data Retransmission
Interval)
3 Bytes
Byte 1: 00
Byte 2-3: interval time, unit:s
range: 30~1200s (600s by default)
Example:
1. Set reporting interval as 20 minutes.
ff8e001400
Channel
Type
Value
ff
8e (Reporting Interval)
14 00 => 00 14 = 20 minutes
2. Reboot the device.
ff10ff
Channel
Type
Value
ff
10 (Reboot)
ff (Reserved)
3. Set time zone.