9 AMAX-5070 User Manual
Chapter 2 AMAX-5070 Modbus/TCP Coupler with ID Switch
2.1.1 General
Certification: CE, FCC class A
Connector: Pluggable 4P push-in terminal (#24~16 AWG) and 2x RJ45
Module Enclosure: Polycarbonate + Aluminum Alloy
Protocol: Modbus TCP
Transmission Rate: 100Mbps
LED Indicator: PWR, RUN, Power Diagnosis LED
Weight: Approx. 190g
2.1.2 Power Input
Rated Voltage: 24VDC (±20%)
Dual Power Input: Supported
Max Current on Bus: 2A
Diagnosis Function:
Over/under voltage for input 1&2
Over current output on bus
2.1.3 Modbus/TCP Coupler
Function: Coupling AMAX-5000 EtherCAT IO Module to Modbus/TCP network
Cable: Ethernet/EtherCAT cable (min. Cat. 5), shielded
Distance between stations: Max. 100 m (100BASE-TX)
Interface: 2 x RJ45,
LAN1: Modbus/TCP,
LAN2: Modbus/TCP (default) or EtherCAT Cable Redundancy
TCP Connection No.: 16
Response Time: 5ms
IO Configuration: Advantech I/O Module Utility
Maximum IO Modules: 256 (excluding AMAX-5079)
Group ID Support: 0~255 (maximum 20 groups)
2.1.4 Environment
Operation Temperature: -25~60°C (vertical mounted)
Storage Temperature: -40~85°C
Relative Humidity: 95% (non-condensing)
Storage Humidity: 95% (non-condensing)
2.1.5 Reliability Test
High Temperature Test: IEC 68-2-78
Low Temperature Test: IEC 68-2-2
Random Vibration Test: IEC 68-2-64
Shock Test: IEC 68-2-27
Package Drop Test: Federal Standard