STARTUP MANUAL
1 Startup Manual
ADAM-6260
6-ch Relay Output Modbus TCP Module
Notes
For more information on this and other Advantech
products, please visit our websites at:
http://www.advantech.com
http://www.advantech.com/eAutomation
For technical support and service:
http://www.advantech.com.tw/eservice
This startup manual is for the ADAM-6260/6266
Part No:
2003626600
1st Edition
February 2013
Switch Settings
It mainly presents the switch conguration for Dry Contact
and Wet Contact wiring in Digital Input interface.
Switch SW2
Position
1 2 3 4
DI Channel
Ch0 Ch1 Ch2 Ch3
ON
Dry Contact (Default)
OFF
Wet Contact
Overview
Thank you for purchasing this ADAM-6200 series
module.This is a quick guide to help you deploy the
ADAM-6200 series module in your application eld. It
will include power and application wiring. If you need a
more complicated or specic installation, you could try
to contact ADVANTECH for advanced technical support
or suggestions.
Input Power Requirements
The ADAM-6200 system is designed for a standard
industrial unregulated 24 V
DC
power supply. For further
applications, it can also accept +10 to +30 V
DC
of power
input, 200mV peak to peak of power ripple, and the
immediate ripple voltage should be maintained between
+10 and +30 V
DC
.
ADAM-6266
4-ch Relay Output Modbus TCP Module with 4-ch DI
Application Wiring
Isolated Digital Input
Dry Contact
Isolated Relay Output
Contact Rating: 250 V
AC
@ 5A, 85°C
30 V
DC
@ 5A, 85°C
Wet Contact