Advantech ADAM-6260 handleiding

64 pagina's
PDF beschikbaar

Handleiding

Je bekijkt pagina 62 van 64
ADAM-6000/6200 RESTful User Manual
62
<VALUE>410</VALUE>
</AI>
<AI>
<ID>1</ID>
<VALUE>410</VALUE>
</AO>
</ADAM-6224>
POST http://10.0.0.1/analogoutput/4/value or
AO=00FF&
Eg=1000
POST http://10.0.0.1/analogoutput/all/value
AO0=00FF&
AO1=0000&
Eg0=1000&
Eg1=1.543
POST Response.
The result. If successful, the result will be "OK"; otherwise, the result will be the error
message.(refer HTTP Response Status-Code)
<ADAM-6224status="OK">
</ADAM-6224>
Resource value definitions :
Field
Abbreviation
Data Type
Property
Description
Channel Number
ID
Number
R
0, 1, …: Analog input channel number.
Channel Raw Value
VALUE
Number
RW
0 ~ FFF : AO measurement data (Raw data of
Hex type)
Set Channel Raw
Value
AOn
Number
W
Set the AO measurement data (Raw data of
Hex type)
n : 0 ~ : the channel number
In the POST all, a channel number is
required, while in the POST a single
channel, a channel number is not
necessary