Advantech ADAM-6260 handleiding
Handleiding
Je bekijkt pagina 60 van 64

ADAM-6000/6200 RESTful User Manual
60
Channel Raw Value
VALUE
Number
R
0 ~ FFF : AO measurement data (Raw data of
Hex type)
Set Channel Raw
Value
AOn
Number
W
Set the AO measurement data (Raw data of
Hex type)
n : 0 ~ : the channel number
⚫ In the POST all, a channel number is
required, while in the POST a single
channel, a channel number is not
necessary
Get / Set Channel
Engineering data
Egn
Number
RW
AO engineering data, the value is measured in
millimeters as the base unit". Unit: V or mA
For example,
1120 1.12 (V)
3.225 3.225 (mA)
n : 0 ~ : the channel number
➢ Only displayed when GET a single channel
➢ In the POST all, a channel number is
required, while in the POST a single
channel, a channel number is not
necessary
Remarks
Both “Set Channel Raw Value” and “Set Channel Engineering data” can set AO
value. When two of them are posted simultaneously that the AO value will be
determined base on the last input.
e.g. POST http://10.0.0.1/analogoutput/all/value
AO0=00FF&
AO1=0000&
Eg0=1000&
Eg1=1.543
The AO value with channel 0 will be determined base on Eg0 , and channel 1 is
Eg1.
e.g. POST http://10.0.0.1/analogoutput/all/value
Eg0=1000&
Bekijk gratis de handleiding van Advantech ADAM-6260, stel vragen en lees de antwoorden op veelvoorkomende problemen, of gebruik onze assistent om sneller informatie in de handleiding te vinden of uitleg te krijgen over specifieke functies.
Productinformatie
Merk | Advantech |
Model | ADAM-6260 |
Categorie | Niet gecategoriseerd |
Taal | Nederlands |
Grootte | 8449 MB |