Advantech ADAM-6260 handleiding
Handleiding
Je bekijkt pagina 54 van 64

ADAM-6000/6200 RESTful User Manual
54
➢ Resource value definitions :
Field
Abbreviation
Data Type
Property
Description
Channel
Number
ID
Number
R
0, 1, …: Analog input channel number.
Output Range
Rng
Number
RW
Analog output range.
Range
code
328
(0x0148) 0 - 10 V
384
(0x0180) 4 ~ 20 mA
386
(0x0182) 0 ~ 20 mA
➢ If POST all, set to all channel at the same
time
Startup Value
AoIV
Number
RW
Set/get the startup value
Value range: 0 ~ 4095
➢ If POST all, set to all channel at the same
time
Remarks
ADAM-6224
Description
Retrieves information about the analog input configuration resource.
GET
http://10.0.0.1/analogoutput/(all|{id})/config
where id = 0 ~ : the channel number
POST
http://10.0.0.1/analogoutput/(all|{id})/config
where id = 0 ~ : the channel number
Some configuration variables will only be displayed or set under specific request. The following table
illustrates the relationship between variables and request:
GET/id
GET/all
POST/id
POST/all