ADAM-6000/6200 RESTful User Manual
41
If POST all, set to all channel at the same
time
Maximum AI Raw
Value
HVal
Number
R
AI max. measurement data (Raw data of Hex
type)
Only displayed when GET a single channel
Minimum AI Raw
Value
LVal
Number
R
AI min. measurement data (Raw data of Hex
type)
Only displayed when GET a single channel
Clear Maximum AI
Raw Value
ClrH
Number
W
1 : Clear the Maximum AI raw value
(clear would be done at the rising edge)
If POST all, set to all channel at the same
time
Clear Minimum AI
Raw Value
ClrL
Number
W
1 : Clear the Minimum AI raw value
(clear would be done at the rising edge)
If POST all, set to all channel at the same
time
Channel
Engineering data
(floating type)
EgF
Number
R
AI engineering data, the value is floating type.
Unit:
mV or mA
For example,
9.120 9.12 mV or
-3.220 -3.22 mA
Only displayed when GET a single channel
Maximum AI
Engineering data
(floating type)
HEgF
Number
R
AI max. engineering data, the value is is
floating type. Unit: mV or mA
For example,
10.200 10.2 mV
-5.120 -5.12 mV
Only displayed when GET a single channel
Minimum AI
Engineering data
(floating type)
LEgF
Number
R
AI min. engineering data, the value is floating
type. Unit: mV or mA
For example,
250.350 250.35 mV