Advantech ADAM-6260 handleiding
Handleiding
Je bekijkt pagina 37 van 64

ADAM-6000/6200 RESTful User Manual
37
POST Response.
The result. If successful, the result will be "OK"; otherwise, the result will be the error
message.(refer HTTP Response Status-Code)
<ADAM-6024status="OK">
</ADAM-6024>
➢ Resource value definitions :
Field
Abbreviation
Data Type
Property
Description
Channel
Number
ID
Number
R
0, 1, …: Analog input channel number.
Channel Enable
En
Number
RW
1 / 0: Enable / Disable AI conversion
➢ Only displayed when GET a single
channel
➢ If POST all, set to all channel at the same
time
Input Range
Rng
Number
RW
Analog input range.
Notice: Average channel is read only.
Range
code
323
(0x0143) +/- 10 V
384
(0x0180) 4 ~ 20 mA
386
(0x0182) 0 ~ 20 mA
➢ If POST all, set to all channel at the same
time
AI Filter Mode
AiT
Number
RW
The AI filter mode
0
Auto (50/60Hz)
1
60 Hz
2
50 Hz
3
High Speed
➢ Only displayed when GET and POST all
channel