ADAM-6000/6200 Series MQTT User Manual
29
%aaGETMQTTAICH
or
%aaGETMQTTAOCH
3.13 Pub/Sub Topic
ADAM module supports topic: 1. Will Topic2. Profile Topic3.Channel Type Topic4. Control Topic
5. All Data Topic6. Channel Config Topic7. Channel Value Topic8. Network Setting Topic9. Access
Control Topic10. User-defined Modbus address Topic11. OTA for Firmware/Configuration File
3.13.1 Will Topic
When the Module actively connects/disconnects with the broker, the module will publish a will topic with
connect/disconnect message. Or when an accident occurs between the module and the broker and abnormal
disconnection happens, the broker will publish a will topic with disconnect message.
Will Topic name: Advantech/{mac}/Device_Status
Will message payload example:
{"status":"connect","name":"ADAM6050","macid":"00D0C9FEAC13","ipaddr":"172.16.12.36"}
3.13.2 Profile Topic
Description
Device sends device information including the I/O module slots.
PUBLISH Topic
Device sends the current configurations.
Advantech/{MAC}/cfg/sensor/profile
Example
Send Advantech/00D0C9CC0099/ cfg/sensor/profile
{
"SL": 0,
"Id": "ADAM-6050",
"DIn": 8,
"DOn": 2,
"RLAn": 0,
"AIn": 0,
"UIn": 0,