Adam/Apax .NET utility. Then the MQTT message from ADAM-6000/6200 modules will come with the
username and password to access the broke
➢ If set null module will disable the username and password function.
➢ Utility changed to display user name and password in plain text in B16, and the old version is displayed
with *。
➢ When connected to the broker, using SET will actively publish the will topic (status: disconnect) and
reconnect.
➢ Starting from following version, the maximum length of user name and password will be modified to 199
characters (the original maximum length was 50 characters), and the storage location of flash will be
adjusted. When the old version is upgraded to this version, the user name and password will be
inherited, but when the new version is downgraded to the old version, user name and password changed
to default (user name: Advantech, password:00000000)
ADAM
DIO
ADAM-
6017/6217
ADAM-
6018+
ADAM-
6024
ADAM-
6224
V6.11 B04
V6.11 B04
V6.01B24
V6.01B19
V6.01B23
ASCII command:
Command
Description
Remarks
%aaSETMQTTUNxx…x*
aa: always 01
xx…x: user name
(0~199 character)
Return: >01
Error: ?01
%aaGETMQTTUN*
aa: always 01
Return: !UserName
Error: ?01
%aaSETMQTTPWxx…x*
aa: always 01
xx…x: password
(0~199 character)
Return: >01
Error: ?01
%aaGETMQTTPW*
aa: always 01
Return: !Password
Error: ?01
3.4 Heartbeat
The broker will regularly check the connection with the ADAM at the heartbeat interval (keep-alive)
setting. Default: 5 second
➢ EdgeSync 360/ EdgeHub don’t use this setting,fixed as 300 second。