Advantech ADAM-6217 handleiding
Handleiding
Je bekijkt pagina 15 van 159

ADAM-6000/6200 Series MQTT User Manual
15
Bit 4
Username or password is incorrect. When the broker is set up with
mosquitto and an account is set, this alarm will appear if the Utility's
account is set incorrectly.
Bit 5
User is not authorized. Ex. This alarm will appear if the account
password is incorrect when connecting to EdgeSync360/ EdgeHub,
or if the Connection String is connected to Azure.
Bit 6
The Broker disconnected after being connected. This alarm will
appear when the Broker is abnormal after there has been a correct
connection.
Bit 7
When Cipher Suites for TLS cannot be paired. This alarm occurs
when the Cipher Suites supported by the Broker do not match the
Cipher Suites supported by the module.。
Bit 8
This alarm occurs when the CA certificate fails to verify the Server
certificate
Bit 9
This alarm occurs when there is a problem with the validity date of the
Server certificate or the SNTP time of the module is wrong.
Bit 10
This alarm occurs when there is a problem with the expiration date of the
Server certificate or the SNTP time of the module is wrong.
(Bit 2 ~ Bit 5 alarm definition is based on MQTT v3.1.1 error definition)
Figure 6. MQTT diagnostic event table
➢ Diagnostic Information contents :
1. Publish or Subscribe
2. Host IP (Source or Destination)