Advantech ADAM-5095 handleiding

96 pagina's
PDF beschikbaar

Handleiding

Je bekijkt pagina 38 van 96
ADAM-5000 Series User Manual 30
Table 3.3: Calibration Voltage of ADAM-5018P
Module Input Range Code
(Hex)
Input Range Span Calibration
Voltage
5018P 00h ±15 mV +15 mV
01h ±50 mV +50 mV
02h ±100 mV +100 mV
03h ±500 mV +500 mV
04h ±1 mV +1 V
05h ±2.5 V +2.5 V
06h ±20 mV +20 mA (1)
07h 4 ~ 20 mA +16 mA (1)
0Eh J thermocouple 0 to 1370°C +50 mV
0Fh K thermocouple 0 to 1370°C +50 mV
10h T thermocouple -100 to 400°C +22 mV
11h E thermocouple 0 to 1000°C +80 mV
12h R thermocouple 500 to 1750°C +22 mV
13h S thermocouple 500 to 1800°C +22 mV
14h B thermocouple 500 to 1800°C +152 mV
Table 3.4: Calibration Voltage of ADAM-5017UH
Module Input Range Code
(Hex)
Input Range Span Calibration Voltage
5017H 08h ±10 V +10 V
48h 0 ~ 10 V +10 V
46h 0 ~ 20 mA *(1)
07h 4 ~ 20 mA *(1)
Note! You can substitute 2.5 V for 20 mA if you remove the current conversion
resistor for that channel. However, the calibration accuracy will be lim-
ited to 0.1% due to the resistor's tolerance.