ADAM-5000 Series User Manual 32
7. Issue the 4 mA Calibration command to indicate that the output is calibrated
and to store the calibration parameters in the module's EEPROM.
8. Execute an Analog Data Out command with an output value of 20 mA. The
module's output will be approximately 20 mA.
9. Execute the Trim Calibration command as often as necessary until the output cur-
rent is equal to exactly 20 mA.
10. Execute the 20 mA Calibration command to indicate that the present output is
exactly 20 mA. The analog output module will store its calibration parameters in
the unit's EEPROM.