ADAM-5000 Series User Manual 28
7. Click “Span” and apply the voltage as pop out windows to the Ch-0 and click
“Apply.”
Note! Zero calibration and span calibration must be completed before CJC
calibration. To calibrate CJC, the thermocouple attached to ADAM-5018
and a standard thermometer should be used to measure a standard
known temperature, such as the freezing point of pure water. The
amount of offset between the ADAM-5018 and the standard thermome-
ter is then used in the ADAM utility to complete CJC calibration.