EtherCAT Run LED (Green)
Indicator states Slave state Condition
Off INITIALISATION The device is in state INIT
Blinking PRE-OPERATIONAL The device is in state PRE-OPERATIONAL
Single Flash SAFE-OPERATIONAL The device is in state SAFE-OPERATIONAL
On OPERATIONAL The device is in state OPERATIONAL
Flickering BOOTSTRAP
The device is booting and has not yet entered the INIT state,
or: The device is in state BOOTSTRAP.
Firmware download operation in progress
EtherCAT Err LED (Red)
Indicator
states
Error Name Description Example
Off No error The device is in working
condition
Blinking Invalid Configuration General configuration
error
State change commanded by
master is impossible due to
register or object setting, or
invalid hardware configuration
(pin sharing violation detected
by ESC)
Single Flash Local error Slave device application
has changed the EtherCAT
state autonomously, due
to local error. Error
Indicator bit is set to 1 in
AL Status register.
Device changes its EtherCAT
state from OpMode to
SafeOpError due to a
synchronization error.
Double
Flash
Process Data Watchdog
Timeout/ EtherCAT
Watchdog Timeout
An application watchdog
timeout has occurred.
Sync Manger Watchdog
timeout.
System/STS LED (white)
Indicator
states
Indicator color Description
Off White The device is not power on.
Blinking Green The device is in working condition
Blinking Orange The device is in abnormal condition.
For instance:
Chapter 1 Understanding Your System
21