27 ADAM-4100 User Manual
Chapter 3 I/O Modules
Accuracy:
Voltage mode: ±0.1% or better
Current mode: ±0.2% or better
Zero drift: ±6 µV/°C
Span drift: ±25 ppm/°C (typical)
CMR @ 50/60 Hz: 92 dB min
Built-in dual watchdog timer
Built-in TVS/ESD protection
Power consumption 1.2 W @ 24 V
DC
Protection (B version)
ESD (IEC 61000-4-2) 8 kV (air)
EFT (IEC 61000-4-4) 4 kV (power line)
Surge (IEC 61000-4-5) power 4 kV (power line)
Jumper/Switch Settings
To simplify the jumper settings, for the ADAM-4117 (B and C version), you can set
whether the analog input type is voltage or current by adjusting the switch instead of
opening the case.
Figure 3.3 ADAM-4117-B/C Switch Settings
Switch SW1 SW2
Analog input channel CH0 CH1 CH2 CH3 CH4 CH5 CH6 CH7
Switch ON Current input mode
Switch OFF (default) Voltage input mode